關閉
您的詢價車是空的。
型號 | RSP-1600-12 | RSP-1600-24 | RSP-1600-27 | RSP-1600-36 | RSP-1600-48 | |
輸出 | 直流電壓 | 12V | 24V | 27V | 36V | 48V |
額定電流 | 125A | 67A | 59A | 44.5A | 33.5A | |
電流範圍 | 0 ~ 125A | 0 ~ 67A | 0 ~ 59A | 0 ~ 44.5A | 0 ~ 33.5A | |
額定功率 | 1500W | 1608W | 1593W | 1602W | 1608W | |
紋波與噪聲(最大) 備註2 | 150mVp-p | 200mVp-p | 200mVp-p | 250mVp-p | 300mVp-p | |
電壓調整範圍 | 11.5 ~ 15V | 23.5 ~ 30V | 26.5~ 33.5V | 35.5~ 45V | 47.5 ~ 58.8V | |
電壓精度 備註4 | ±1.0% | ±1.0% | ±1.0% | ±1.0% | ±1.0% | |
線性調整率 | ±0.5% | ±0.5% | ±0.5% | ±0.5% | ±0.5% | |
負載調整率 | ±0.5% | ±0.5% | ±0.5% | ±0.5% | ±0.5% | |
啟動、上升時間 | 1500ms, 60ms/230VAC(滿載時) | |||||
保持時間(Typ.) | 16ms / 230VAC(75%負載) 10ms / 230VAC(滿載時) | |||||
輸入 | 電壓範圍 備註5 | 90 ~ 264VAC 127 ~ 370VDC | ||||
頻率範圍 | 47~63Hz | |||||
功率因子(Typ.) | 0.97/230VAC(滿載時) | |||||
效率(Typ.) | 89% | 91.5% | 92% | 92% | 93% | |
交流電流(Typ.) 備註5 | 14A/115VAC 8A/230VAC | 15A/115VAC 8.5A/230VAC | ||||
浪湧電流(Typ.) | 冷啟動:35A/230VAC | |||||
漏電流 | <2.0mA / 240VAC | |||||
保護 | 過負載 | 額定輸出功率的105~115% | ||||
保護類型 :恆流限制模式,5 秒後關閉 O/P 電壓。 O/P電壓下降後,重啟恢復 | ||||||
過電壓 | 15.75 ~ 18.75V | 31.5 ~ 37.5V | 35.2 ~ 41.9V | 47.2 ~ 56.3V | 63 ~ 75V | |
保護類型 :關閉輸出電壓,重啟後恢復 | ||||||
過溫度 | 關閉輸出電壓,溫度下降後自動恢復 | |||||
功能 | 輸出電壓調整(PV) 備註6 | 輸出電壓可以在40 ~ 125%額定輸出範圍內調整(12V為60~125% ), 請參考功能手冊 | ||||
恆流值調整(PC) 備註6 | 恆流值可以在20~100%額定電流範圍內調整, 參照功能手冊 | |||||
輔助電源 | 5V @ 0.3A / 12V @ 0.8A | |||||
遙控開關 | 通過電子信號或乾觸點 電源啟動:短路 電壓關閉:開路, 請參考功能手冊 | |||||
遙感 | 遙感對負載線壓降補償最大為0.5V, 請參考功能手冊 | |||||
故障信號 | T-Alarm和DC-OK隔离TTL信号输出 | |||||
環境 | 工作溫度 | -30~+70℃ (請參考"減額曲線") | ||||
工作濕度 | 20 ~ 90% RH,無冷凝 | |||||
儲存溫度、濕度 | -40 ~ +85℃, 10 ~ 95% RH | |||||
溫度係數 | ±0.03%/℃ (0 ~ 50℃) | |||||
耐震動 | 10 ~ 500Hz, 2G 10分鐘/週期, X、Y、Z軸各60分鐘 | |||||
安規和電磁兼容 | 安全規範 | UL62368-1, CAN/CSA C22.2 No. 62368-1, TUV BS EN/EN62368-1, BSMI CNS14336-1, AS/NZS62368.1, EAC TP TC 004認證通過 | ||||
耐壓 | I/P-O/P:3KVAC I/P-FG:2KVAC O/P-FG:1.5KVAC | |||||
絕緣阻抗 | I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25℃/ 70% RH | |||||
電磁兼容發射 | 參數 | 標準 | 測試等級/備註 | |||
Conducted | BS EN/EN55032 (CISPR32) | Class B | ||||
Radiated | BS EN/EN55032 (CISPR32) | Class A | ||||
Harmonic Current | BS EN/EN61000-3-2 | Class A | ||||
Voltage Flicker | BS EN/EN61000-3-3 | ----- | ||||
電磁兼容抗擾度 | BS EN/EN55024, BS EN/EN61000-6-2, BSMI CNS13438 | |||||
參數 | 標準 | 測試等級/備註 | ||||
ESD | BS EN/EN61000-4-2 | Level 3, 8KV air ; Level 2, 4KV contact | ||||
Radiated | BS EN/EN61000-4-3 | Level 3 | ||||
EFT / Burst | BS EN/EN61000-4-4 | Level 3 | ||||
Surge | BS EN/EN61000-4-5 | Level 4, 2KV/Line-Line 4KV/Line-Earth | ||||
Conducted | BS EN/EN61000-4-6 | Level 3 | ||||
Magnetic Field | BS EN/EN61000-4-8 | Level 4 | ||||
Voltage Dips and Interruptions | BS EN/EN61000-4-11 | >95% dip 0.5 periods, 30% dip 25 periods, >95% interruptions 250 periods | ||||
其他 | MTBF | 478.8K hrs Telcordia SR-332 (Bellcore) ; 42.1K hrs MIL-HDBK-217F (25℃) | ||||
尺寸 | 300*85*41mm (L*W*H) | |||||
包裝 | 2.1Kg | |||||
備註 | 1. 如未特別說明,所有規格參數均在輸入為230VAC、額定負載、25℃環境溫度下進行量測。 2. 紋波和噪聲測量方法:使用一條12"雙絞線,同時終端要並聯0.1uf和47uf的電容,在20MHZ帶寬下進行量測。 3. 在超過一台整機並聯操作下,若輕負載使用情況時,有可能輸出紋波大於規格值,只要負載大於5%則輸出紋波將恢復正常。 4. 精度:包含設定誤差、線性調整率和負載調整率。 5. 低電壓輸入情況下需減額輸出,具體請參照輸出減額曲線圖。 6. 當用戶不使用於PMBus/CANBus時進入PV/PC 功能模式,當使用於PMBus/CANBus或PV/PC 時則進入SVR功能模式。 7. 輸出電壓低於 Vset 的 80% 以下 5 秒後,輸出將關閉,重新上電恢復。 8. 電源應視為系統內元件的一部分,所有的EMC測試都將測試樣品安裝在一個厚度1mm,長720mm*寬360mm的金屬鐵板上測試。 電源需結合終端設備進行電磁兼容相關確認。有關EMC測試操作指導,請參閱“組件電源供應器的EMI測試”。 (在明緯網站http://www.meanwell.cc ) 9. 當海拔高度超過2000米(6500英尺)時,無風扇機型環境溫度依每3.5℃/1000m比例下降,有風扇機型環境溫度依每5℃/1000m比例下降。 ※ 產品免責聲明:詳情請參閱 http://www.meanwell.cc/serviceDisclaimer.aspx |